ICM50000
THREE WAY ISOLATED SERIAL CONVERTER MODULE (RS-232/RS-485)
Product availability: Against PO
FEATURES
- Three Way Isolation protects serial equipment from ground loops (1000 VDC)
- Modular RJ jack or screw terminals for RS-485 connection
- 9-pin D-SUB for RS-232 Connection
- Selectable DTE & DCE Operation – Works with any RS-232 cable
- Selectable Baud Rates from 9600 to 115200
- LED Indication for RXD,TXD, and Power
- Half Duplex (RS-485) and Full Duplex (RS422)
- 9 to 26 VDC Power
DOWNLOAD
SPECIFICATIONS
| POWER | +9 to 26 VDC @ 125 mA maximum. 85 mA typical Power Supply must be Class 2 or SELV rated |
| RS-232 VOLTAGES: | |
| Receive Data Pin |
± 30 VDC max
|
| Mark Condition |
≤ 0.8 VDC
|
| Space Condition |
≥ 2.4 VDC
|
| Transmit Data Pin |
± 30 VDC max
|
| Mark Condition |
-8 VDC (typ.)
|
| Space Condition | +8 VDC (typ.) |
| RS-485 VOLTAGES: | |
| Differential Output Voltage | ± 5 VDC max. under no load |
| Differential Input Voltage | ± 5 VDC max |
| Mark Condition | ≤ -0.2 VDC |
| Space Condition | ≥ +0.2 VDC |
| RS-485 Drive Capability | Up to 32 RS-485 receivers connected in parallel |
| RS-485 Drive Disable Time | one character time (at the set baud rate) |
| MAXIMUM CABLE LENGTH: | |
| RS-232 | 50 feet (15.24 m) |
| RS-485 | 4000 feet (1219.2 m) |
| BAUD RATE: | 9600 min., 115200 max |
| ISOLATION: | 1000 VDC |
| ENVIRONMENTAL CONDITIONS: | |
| Operating Temperature Range | 0 to 50°C |
| Storage Temperature | -40 to + 75°C |
| Operating and Storage Humidity | 85% max. relative humidity (non-condensing) from 0 to 50°C |
| Vibration to IEC 68-2-6 | Operational 5 to 150 Hz, 2 g |
| Shock to IEC 68-2-27 | Operational 30 g |
| Altitude | Up to 2000 meters |
| CONSTRUCTION: | Case body is black, high impact plastic. Installation Category I, Pollution Degree 2 |
| MOUNTING: | Standard DIN rail top hat (T) profile rail according to EN50022- 35 X 7.5 and 35 X 15 |
| WEIGHT: | 3.3 oz. (93.6 g) |