E3-MIX20884-1
The highly rugged E3 I/O modules feature discrete, analog and temperature I/O, dual Ethernet ports, an RS-485 serial port and one USB port. Configured via web interface or Red Lion’s award winning Crimson 3.0 software,E3 I/O modules are easy to setup and deploy
Product Availability: AGAINST PO, WITHIN 3-4 WEEKS
FEATURES
- Wide Variety of I/O Configurations
- 17 models with various discrete, analog and temperature I/O
- Powerful Networking Capabilities
- Built-in two port Ethernet switch for daisy chaining, redundancy, or pass-through
- Modbus protocol support for industrial monitoring and communications
- Built-in Security for Proactively Blocking Unwanted Access
- RS-485 Port for Connecting Serial Devices to Ethernet Network
- Industrial Design Supporting Deployment in Extreme Environments
- Hardened metal enclosure with both DIN-rail and panel mount options
- Wide -40° to 75°C operating temperature range
- UL/cUL Class 1, Division 2 Listed
- Configured via Crimson software for easy point-and-click configuration or through built-in web interface.
DOWNLOAD
SPECIFICATIONS
SWITCH PROPERTIES | |
Operation | Monitored. |
IEEE Compliance |
802.3, 802.3u, 802.3ab, 802.3x 802.1d/D/w, 802.1p, 802.1Q, 802.1x
|
Protocols | TCP/IP, ARP, UDP, ICMP, DHCP, HTTP, Modbus TCP, Modbus UDP (slave or master), Sixnet TCP, Sixnet UDP (slave or master) |
Latency (typical) | 5 us @ 100 Mbps |
Switching Method | Store-and-Forward |
Networks | 1 or 2 independent with unique MAC and IP addresses |
Real-Time Ring | 30 ms + 5ms per hop MDIX Auto Sensing Cable Auto Sensing Speed and Flow Control |
POWER INPUT | |
Input Voltage | 10-30 VDC (12-24 Nominal) |
Steady Input Current | Maximum: 355mA @ 24VDC no loads |
Average: 190mA @ 24VDC no loads | |
Minimum: 150mA @ 24VDC no loads | |
Max Inrush | 5 A /100 us @ 24 VDC BTU/HR: 8 (typical) |
CONNECTORS | |
Ethernet Ports | Two (2) 10/100Base-T(X) RJ45 ports |
Serial Port: | One (1) RS-485 screw block (485+, 485-, GND; 2-wire half-duplex, non-isolated) RS-485 |
Networking | Up to 32 (full load) stations RS-485 |
Distance | Up to 0.5 miles (baud-rate dependent) |
Baud Rates | 300 to 57,600 baud |
Rates | 300 to 57,600 baud Protocols: Master and slave; Sixnet and Modbus RTU/ASCII |
DISCRETE INPUTS | |
Voltage Range |
Voltage Range: 10-30 VDC or 60-140 VAC
|
Input Resolution | 150 volts (16 channel modules only) |
Input Resistance | 10 Kohms |
Response | Slow Response:25 ms (20 Hz max count rate) |
Fast Response:1 ms (400 Hz max count rate) | |
Special Fast Counting | Up to 50 KHz (channel 1 & 2) |
Count Up | Pulse timing and pulse rate 16 or 32-bit reporting |
ENVIRONMENTAL CONDITIONS | |
Operating Temperature | -40° to +75°C |
Storage Temperature | -40° to 85°C |
Operating Humidity | 10% to 95% (Non Condensing) |
Vibration | IEC60068-2-27 |
Shock | IEC60068-2-6 |
CERTIFICATIONS AND COMPLIANCES | Hazardous Locations: ANSI/ISA 12.12.01-2013 Edition (Class I, Div. 2, Groups A, B, C, and D), CSA C22.2/213;
Marine/Offshore: Rated per ABS, DNV and Lloyds Electrical Safety: UL 508, CSA C22.2/142, EN/IEC61010-1, CE EMI Emissions: FCC part 15, ICES-003, Class A, EN-55022; EN6100-6-4, CE EMC Immunity: EN61000-6-2, CE (EN61000-4-2,3,4,5,6,8); CE Flammability: UL 94V-0 materials. |