EPAX0500

Red Lion’s EPAX 4 inch (101 mm) high LED displays are easily read from a distance of up to 180 feet. The input to this display is selected from a variety of input modules that can be installed in the field. The input modules include count, rate, time, voltage, current, process, temperature, and strain gage modules.

Product Availability: AGAINST PO

Country Of Origin : Taiwan

FEATURES

  • LARGE LED DISPLAY READABLE TO 180 FEET
  • VARIOUS ANALOG INPUT MODULES
  • DC VOLTAGE AND CURRENT
  • PROCESS SIGNALS
  • TRUE RMS VOLTAGE AND CURRENT
  • THERMOCOUPLE OR RTD
  • STRAIN GAGE/BRIDGE
  • ALARMS, ANALOG OUTPUT, AND COMMUNICATION
  • PROGRAMMABLE USER INPUTS
  • UNIVERSAL AC POWERED (85 to 250 VAC)
  • CRIMSON PROGRAMMING SOFTWARE
  • NEMA 4X/IP65
DISPLAY :  4″ (101 mm) Red LED 5-Digit (EPAX0500): -19999 to 99999
POWER REQUIREMENTS: AC MPAX Modules: 85 to 250 VAC, 50/60 Hz, 18 VA EPAX Display: 85 to 250 VAC, 50/60 Hz, 10 VA
INPUT : Accepts analog input modules,
ANNUNCIATORS: Display Indication: Three vertical dots on the left side of the unit identify the displays for the following modes: Setpoint Indication: Four vertical dots on the right side of the unit identify the setpoint “ON” condition, with SP 1 being the top position through SP 4 at the bottom.Display Indication: Three vertical dots on the left side of the unit identify the displays for the following modes

Setpoint Indication: Four vertical dots on the right side of the unit identify the setpoint “ON” condition, with SP 1 being the top position through SP 4 at the bottom.

EPAX Programming : The unit is a large display, designed to be remotely mounted. Therefore, the unit does not have a programming keypad. Unit programming should be accomplished by one of the following methods:

Rear Terminal Block: External switches can be wired via the terminal block to allow unit programming. A minimum of 3 switches would be required.

Optional Programming Remote (EPAXPGM0): This option provides a 10 foot interconnecting cable and programming box. The Programming Remote contains buttons similar to the PAX, allowing easy programming of the EPAX display.

Optional Serial Programming: Like all PAX units, you can purchase an RS232 or RS485 Comms Card and program the unit via Crimson, a Windows® based software program.

CERTIFICATIONS AND COMPLIANCES : SAFETY UL Recognized Component, File #E179259,

UL61010A-1, CSA C22.2 No. 1010-1

Recognized to U.S. and Canadian requirements under the Component Recognition Program of Underwriters Laboratories, Inc.

UL Listed, File #E137808, UL508, CSA C22.2 No. 14-M95 LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards

Type 4X Indoor Enclosure rating (Face only), UL50 IECEE CB Scheme Test Certificate #US/8843A/UL

CB Scheme Test Report #04ME11209-20041018 Issued by Underwriters Laboratories, Inc. IEC 61010-1, EN 61010-1:

Safety requirements for electrical equipment for measurement, control, and laboratory use, Part 1. IP65 Enclosure rating (Face only), IEC 529

MODULE INSTALLATION : 24-pin shrouded connector on EPAX engages connector on MPAX module upon installation. Shroud ensures proper alignment by providing a lead-in for the module connector.
CONNECTIONS : Wiring connections are made to the EPAX terminal block and MPAX module via high compression cage-clamp terminal blocks.

MPAX Module Wiring: Instructions are provided in the corresponding PAX Bulletin.

EPAX Terminal Block Wiring:

  • Wire Strip Length: 0.3″ (7.5 mm)
  • Wire Gage: 30-12 AWG copper wire
  • Maximum Torque: 5-7 inch-lbs (0.58-0.81 N-m).
MOUNTING REQUIREMENTS: Max. panel thickness is 0.375″ (9.5 mm) Min. panel thickness for NEMA 4/IP65 sealing is 0.060″ (1.52 mm)